| Product
Name: |
SCT6023 |
|
| Application: |
Oxidising
Biocide for Recirculating & Once Through Water
Systems |
| Brief
Description: |
US
EPA Registered Oxidising Biocide |
| Format: |
Bottle
(2.05kg) - Solid |
| Description |
SCT6023 is a US EPA registered fungicide, bacteriacide,
algaecide; and molluscicide for recirculating and
once-through water systems. SCT6023 is a halogenated
hydantoin based oxidizing biocide that functions
as an effective microbiocide through the controlled
release of active bromine and chlorine.
SCT6023 is recommended for the control of bacterial,
fungal and algal slimes in evaporative condensers,
re-circulating cooling tower systems, influent systems,
industrial wet scrubber systems, sewage systems,
auxillary water systems, photo processing wash water,
air washers; and brewery pasteurisers. Published
studies demonstrate that the combination of free
and combined halogens provided by SCT6023 is more
efficacious toward biofilm than either free chorine
or free bromine alone. The increased stability of
the combined halogens in systems with high halogen
demand also allows greater diffusion into the biofilm
without loss from unwanted side reactions.
SCT6023 is available in fully recyclable plastic
bottles each containing 2.05kg of concentrated solid
chemical.
SCT6023 contains 1-bromo-3-chloro-5, 5-dimethylhydantoin,
1, 3-dichloro-5, 5-dimethylhydantoin and 1,3-dichloro-5-ethyl-5-methylhydantoin.
Use with SCT6019
SCT6023 is an activator for residual bromide from
the degradation of DBNPA. When SCT6019, which is
based on DBNPA is used as a cooling tower microbiocide
it decomposes to bromide ion. When supplemented
with SCT6023, the bromide ion present in the re-circulating
water is activated to hypobromous acid, effectively
introducing an additional algaecide in to the system.
The use of SCT6019 and SCT6023 combine together
to create a highly effective oxidizing / non-oxidising
bio-control programme.
Both SCT6019 and SCT6023 are US EPA registered.
Chlorine/Bromine Source
SCT6023 can be used on its own as a chlorine/bromine
source.
Available chlorine % Cl2 - 43%
Available bromine % Br2 - 43%
SCT6023 contains no binders and is effective in
both alkaline and acidic pH ranges.
Dosage Rate
For industrial re-circulating cooling water systems
dosage rates for SCT6023 will be dependent on the
conditions of the system prior to treatment. Systems
that are heavily contaminated should be cleaned
prior to product use. Apply SCT6023 to maintain
a free halogen residual in the re-circulating water.
3.6m3 of system volume, dosed at 1 ppm,
would require 5g of SCT6023. Approximately 22 litres
of solution from an SCT approved dissolution system
feeder. There is 0.7g of SCT6023 in 3.6 litres of
solution.
Testing & Control
DPD free/total test kits suitable for monitoring
and controlling the use of SCT6023 are available
from SCT.
Feeding
Feed SCT6023 using an SCT approved system containing
no metal parts that would come in contact with solution
or vapours.
Packaging, Storage and Handling
SCT6023 is packaged in cases containing 4 x 2.05kg
bottles.
Each case weighs 8.2kg.
For all safety data refer to the latest SCT MSDS.
Store this product in cool, dry area. Correctly
stored product will remain effective for between
24 to 36 months.
Additional Information
& Technical Support
For additional product information, application advice,
pricing or technical
support please contact us for further assistance.
|